Schneider Breaker 3Pole, 16A, 10kA, EZC100F, MCCB
Main range of product EasyPact product or component type Circuit breaker device short name Easypact EZC100F circuit breaker name Easypact EZC100F device application Distribution poles description 3P protected poles description 3t network type AC DC network frequency 50/60 Hz [In] rated current 100 A at 40 °C [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 [Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2 breaking capacity code F breaking capacity 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 [Ics] rated service breaking capacity 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category A trip unit name TM-D trip unit technology Thermal-magnetic trip unit rating 16 A at 50 °C protection type Overload protection Short-circuit protection pollution degree 3 conforming to IEC 60947