Schneider Breaker 3Pole, 250A, 25kA, CVS250B, MCCB
Main range of product Easypact CVS100...250 product or component type Circuit breaker device short name CVS250B device application Distribution poles description 3P protected poles description 3d Earth leakage protection (Vigi add on) Without [In] rated current 250 A at 40 °C breaking capacity code B network type AC [Icu] Breaking capacity 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 utilisation category Category A trip unit name TM-D trip unit technology Thermal-magnetic trip unit rating 250 A at 40 °C protection type Short-circuit protection (magnetic) Overload protection (thermal)